Título: | EVALUATION OF THE EFFECTS OF RIPPLE AMPLITUDE IN THE CALIBRATION OF HIGH VOLTAGE STANDARDS IN DIRECT CURRENT | ||||||||||||
Autor: |
FERNANDA DUTRA ALVES |
||||||||||||
Colaborador(es): |
CARLOS ROBERTO HALL BARBOSA - Orientador |
||||||||||||
Catalogação: | 21/JAN/2021 | Língua(s): | PORTUGUESE - BRAZIL |
||||||||||
Tipo: | TEXT | Subtipo: | THESIS | ||||||||||
Notas: |
[pt] Todos os dados constantes dos documentos são de inteira responsabilidade de seus autores. Os dados utilizados nas descrições dos documentos estão em conformidade com os sistemas da administração da PUC-Rio. [en] All data contained in the documents are the sole responsibility of the authors. The data used in the descriptions of the documents are in conformity with the systems of the administration of PUC-Rio. |
||||||||||||
Referência(s): |
[pt] https://www.maxwell.vrac.puc-rio.br/projetosEspeciais/ETDs/consultas/conteudo.php?strSecao=resultado&nrSeq=51301&idi=1 [en] https://www.maxwell.vrac.puc-rio.br/projetosEspeciais/ETDs/consultas/conteudo.php?strSecao=resultado&nrSeq=51301&idi=2 |
||||||||||||
DOI: | https://doi.org/10.17771/PUCRio.acad.51301 | ||||||||||||
Resumo: | |||||||||||||
There is a growing prospect of using high voltage in direct current (HVDC). Thus, based on information from the literature on dielectric tests in equipment for HVDC and requirements regarding the reliability of metrological procedures, this dissertation aims at monitoring and analyzing a specific parameter (ripple) in a way that can guarantee the traceability of reference systems. The reference systems allow only a quantitative analysis of the calibration voltage, being necessary to evaluate and ensure that the measurement uncertainty is not influenced by ripples of up to 3 percent, but it is also necessary to make a qualitative assessment. In the case of HVDC tests, the use of different power supplies and rectifiers causes ripple at different levels, influencing the quality of the supplied voltage and possibly other relevant parameters for the ABNT NBR IEC 60060-1:2013 standard. In this context, the objective of this dissertation was the improvement and validation, with the draft of the IEC 61083-4 standard, of a signal acquisition and processing algorithm developed in LabVIEW that communicates with an 8
(1 over 2) digit multimeter and estimates all the normalized parameters. It is also intended to establish the procedures introduced for HVDC calibration and an analysis of the ripple influence from the parameters defined by the standard. To validate the methodology proposed in this dissertation, tests were made with different arrangements, with universal and purely resistive dividers, and different ripple levels, in the laboratory, statistically comparing the calibration measurement uncertainties with different ripple levels in the traceability of reference systems. Finally, the results indicate that the ripple does not influence the calibration.
|
|||||||||||||
|